+86 15625767518

Features
Specifications
MODEL WP605 WP610 WP615 WP620 WP630
DC INPUT
Rated voltage 12 V 24 V 36 V (S) 48 V (H) 48 V
DC input range (default) 10 ~ 15 V 20 ~ 30 V 30 ~ 45 V (S) 40 ~ 60 V (H) 40 ~ 60V
AC input range (bypass mode)
0 ~ 121 / 132 / 138 / 144 Vac for 100 / 110 / 115 / 120 Vac ± 10 Vac 0 ~ 242 / 264 / 276 / 288 Vac for 200 / 220 / 230 / 240 Vac ± 10 Vac
AC input range (mains mode) 100 V: 70 ~ 130 Vac 110 V: 80 ~ 140 Vac 115 V: 85 ~ 145 Vac 120 V: 90 ~ 150 Vac 200 V: 145 ~ 260 Vac 220 V: 165 ~ 280 Vac 230 V: 175 ~ 290 Vac 240 V: 185 ~ 300 Vac
Frequency input range 50 / 60 Hz (auto-sensing), 50 / 60 Hz ± 5% ~ 15%
Generator connection Available (generator input power is settable)
OUTPUT
Inverter output range 100 / 110 / 115 / 120 / 200 / 220 / 230 / 240 Vac ± 5% (settable)
AC output range (bypass mode) 0 ~ 121 / 132 / 138 / 144 Vac for 100 / 110 / 115 / 120 Vac ± 10 Vac 0 ~ 242 / 264 / 276 / 288 Vac for 200 / 220 / 230 V / 240 Vac ± 10 Vac
AC output range (mains mode) 100 V: 90 ~ 110 Vac 110 V: 99 ~ 121 Vac 115 V: 103 ~ 126 Vac 120 V: 108 ~ 132 Vac 200 V: 166 ~ 226 Vac 220 V: 188 ~ 245 Vac, 230 V: 199 ~ 254 Vac 240 V: 210 ~ 264 Vac
Output frequency 50 / 60 Hz ± 0.3 Hz (settable)
Waveform Pure sine wave
Inverter efficiency Max. 75% Max. 80% Max. 85%
Energy saving mode Settable (< 3% load) , enter in 80 s
No-load shutdown Settable (< 3% load), shut down in 80 s
Transfer time ≤ 10 ms
THDV (resistive load) ≤ 5%
Protections Overload, short circuit (inverter), battery low voltage, battery overcharge, overtemperature
Overload (mains mode) 110% for 120 s, 125% for 60 s, 150% for 10 s (transfer to bypass mode)
Overload (inverter mode) 110% for 60 s, 125% for 10 s, 150% for 5 s (shut down directly)
Mute Automatic mute in 60 s or by manual
BATTERIES
Inbuilt battery (standard model) / 12 V / 7 Ah x 2 12 V / 9 Ah x 2 12 V / 9 Ah x 3 12 V / 9 Ah x 4
Charging current Standard model (S): 1 A (default)
Long time model (H): 10 A (default); < 10 A, set step 1 A; ≥ 10 A, set step 5 A
Max. 10 A (H) Max. 15 A (H) / Max. 20 A (H) Max. 25 A (H)
Equalizing charge voltage Single battery 14.1 Vdc (default), 13.6 ~ 15 Vdc adjustable
Floating charge voltage Single battery 13.5 Vdc (default), 13.2 ~ 14.6 Vdc adjustable
Low voltage alarm point Single battery 10.8 Vdc (default), 9.6 ~ 13 Vdc adjustable
Low voltage shutdown point Single battery 10.2 Vdc (default), 9.6 ~ 11.5 Vdc adjustable
OTHERS
Communications USB & RJ45 (standard), dry contacts / SNMP (optional)
Operating temperature 5℃ ~ 40℃
Operating humidity Relative humidity ≤ 93%
Noise level ≤ 50 dB (1 m)
Tower Dimensions (W × D × H) (mm) 144 x 345 x 215 (S / H) 144 x 410 x 215 (S) 144 x 345 x 215 (H) 157.5 x 460x 221.5(S) 190 x 467 x 335.5 (H)
Packaged dimensions (W × D × H) (mm) 236 x 427 x 316 (S / H) 236 x 492 x 316 (S) 236 x 427 x 316 (H) 238 x 550 x 305 (S) 320 x 592 x 462 (H)
Net weight (kg) 7.0 (H) 12.2 (S) 11.6 (H) 14.2 (S) 18.5 (S) 17.8 (H) 23.6 (S) 28.0 (H)
Gross weight (kg) 8.0 (H) 13.2 (S) 12.6 (H) 15.2 (S) 19.8 (S) 18.8 (H) 25 (S) 30.0 (H)
Rack- mount Dimensions (W × D × H) (mm) -- 440 × 338 × 88 (S) 440 × 410 × 132 (S)
Packaged dimensions (W × D × H) (mm) -- 611 × 448 × 208 (S) 611 × 505 × 235 (S)
Net weight (kg) -- 14.6 (S) 17.2 (S) 21.3 (S) 26.7 (S)
Gross weight (kg) -- 16.8 (S) 20.4 (S) 24.5 (S) 30.5 (S)