+86 15625767518
WP660 modular UPS is ideal for reliable, saving, intelligent and easy solutions. It ensures that a scalable, secure, high quality power supply is available for any critical high-density computer and IT environment applications, such as data centers and other critical loads.
WP660 modular UPS is a scalable three-phase / three-phase uninterruptible power supply system with DSP technology and provides true on-line double conversion power protection. The available UPS power and redundancy level can expand vertically from 50 to 600 kVA / 600 kW in one single power cabinet, and four power cabinets can be connected in parallel, increasing the capacity up to 2.4 M kW. It features modular hot-swappable design, all modules support “plug & play”, including power modules, bypass module, and control module, simplifies UPS servicing and maintenance.
HighlightsMODEL | WP66200 | WP66300 | WP66400 | WP66500 | WP66600 |
Rated capacity | 200 kVA/200 kW | 300 kVA/300 kW | 400 kVA/400 kW | 500 kVA/500 kW | 600 kVA/600 kW |
Numbers of power modules | 4 | 6 | 8 | 10 | 12 |
Rated capacity of power module | 50 kVA | ||||
INPUT | |||||
Input wiring | 3 Ph + N + PE | ||||
Rated voltage | 380 / 400 / 415 Vac | ||||
Voltage range | 138 ~ 485 Vac (304 ~ 485 Vac without power downgrading; 138 ~ 304 Vac with linear downgrading 40%) | ||||
Input frequency | 40 ~ 70 Hz | ||||
Power factor | ≥ 0.99 | ||||
Current distortion | < 3% | ||||
BATTERIES | |||||
Battery voltage | ± 240 Vdc (±180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) | ||||
Number of battery | 40 pcs12 V batteries ( 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable) | ||||
OUTPUT | |||||
Output wiring | 3 Ph + N + PE | ||||
Rated voltage | 380 / 400 / 415 Vac ± 1% | ||||
Frequency | Synchronized with utility in mains power mode: 50 Hz / 60 Hz ± 0.25% in battery mode | ||||
Power factor | 1 | ||||
Voltage distortion | ≤ 1% with linear load / ≤ 3 % with non-linear load | ||||
Crest factor | 3:1 | ||||
Inverter overload capacity | 105% < load ≤ 110%: transfer to bypass in 60 min 110% < load ≤ 125%: transfer to bypass in 10 min 125% < load ≤ 150%: transfer to bypass in 1 min Load > 150%: transfer to bypass in 200 ms | ||||
Bypass overload capacity | Load ≤135% for long term; < 1000% load for 100 ms | ||||
SYSTEM | |||||
Efficiency | 96.5% | ||||
Max. number of parallel connections | 4 units | ||||
Transfer time | 0 ms | ||||
Protections | Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. | ||||
Communications | RS485, dry contacts, SNMP | ||||
Display | 7 inches LCD touch screen | ||||
OTHERS | |||||
Operating temperature | 0 ~ 40℃ | ||||
Storage temperature | -40℃ ~ +70℃ | ||||
Humidity | 0 ~ 95%(non-condensing) | ||||
Altitude | ≤1000 m. Above 1000 m, derating 1% for each additional 100 m | ||||
Protection level | IP 20 | ||||
Noise level at 1 m | < 65 dB | < 68 dB | |||
Cabinet dimensions (W x D x H) (mm) | 600 × 850 × 2000 | 1200 × 850 × 2000 | 1400 × 850 × 2000 | ||
UPS module dimensions (W x D x H) (mm) | 440 × 620 × 130 | ||||
Cabinet weight (kg) | 233 | 242 | 415 | 465 | 617 |
Power module weight (kg) | 32 |