+86 15625767518

WP660 modular UPS is ideal for reliable, saving, intelligent and easy solutions. It ensures that a scalable, secure, high quality power supply is available for any critical high-density computer and IT environment applications, such as data centers and other critical loads.

WP660 modular UPS is a scalable three-phase / three-phase uninterruptible power supply system with DSP technology and provides true on-line double conversion power protection. The available UPS power and redundancy level can expand vertically from 50 to 600 kVA / 600 kW in one single power cabinet, and four power cabinets can be connected in parallel, increasing the capacity up to 2.4 M kW. It features modular hot-swappable design, all modules support “plug & play”, including power modules, bypass module, and control module, simplifies UPS servicing and maintenance.

Highlights
Features
Specifications
MODEL WP66200 WP66300 WP66400 WP66500 WP66600
Rated capacity 200 kVA/200 kW 300 kVA/300 kW 400 kVA/400 kW 500 kVA/500 kW 600 kVA/600 kW
Numbers of power modules 4 6 8 10 12
Rated capacity of power module 50 kVA
INPUT
Input wiring 3 Ph + N + PE
Rated voltage 380 / 400 / 415 Vac
Voltage range 138 ~ 485 Vac (304 ~ 485 Vac without power downgrading; 138 ~ 304 Vac with linear downgrading 40%)
Input frequency 40 ~ 70 Hz
Power factor ≥ 0.99
Current distortion < 3%
BATTERIES
Battery voltage ± 240 Vdc (±180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable)
Number of battery 40 pcs12 V batteries ( 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable)
OUTPUT
Output wiring 3 Ph + N + PE
Rated voltage 380 / 400 / 415 Vac ± 1%
Frequency Synchronized with utility in mains power mode: 50 Hz / 60 Hz ± 0.25% in battery mode
Power factor 1
Voltage distortion ≤ 1% with linear load / ≤ 3 % with non-linear load
Crest factor 3:1
Inverter overload capacity 105% < load ≤ 110%: transfer to bypass in 60 min 110% < load ≤ 125%: transfer to bypass in 10 min 125% < load ≤ 150%: transfer to bypass in 1 min Load > 150%: transfer to bypass in 200 ms
Bypass overload capacity Load ≤135% for long term; < 1000% load for 100 ms
SYSTEM
Efficiency 96.5%
Max. number of parallel connections 4 units
Transfer time 0 ms
Protections Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc.
Communications RS485, dry contacts, SNMP
Display 7 inches LCD touch screen
OTHERS
Operating temperature 0 ~ 40℃
Storage temperature -40℃ ~ +70℃
Humidity 0 ~ 95%(non-condensing)
Altitude ≤1000 m. Above 1000 m, derating 1% for each additional 100 m
Protection level IP 20
Noise level at 1 m < 65 dB < 68 dB
Cabinet dimensions (W x D x H) (mm) 600 × 850 × 2000 1200 × 850 × 2000 1400 × 850 × 2000
UPS module dimensions (W x D x H) (mm) 440 × 620 × 130
Cabinet weight (kg) 233 242 415 465 617
Power module weight (kg) 32