+86 15625767518
This Off-Grid solar system is available in 10KVA ~ 120KVA models with DSP digital control technology, it is combined with pulse-width modulation (SVPWM), disturbance MPPT control and multi-level control technology to enable the system to track the maximum power of solar panels fast. Its secure power supply feature provides good quality power with regulated voltage and frequency to the loads, and it is featured with energy storage and staggering power consumption as well. It is an ideal inverter for medium-sized or large-scale residential, commercial and industrial PV applications which are off the grid, such as village, farm, factory, office building and islands etc.
FeaturesMODEL | 10 KVA | 20 KVA | 30 KVA | 40 KVA | 60 KVA | 80 KVA | 100 KVA | 120 KVA |
Rated power | 9 KW | 18 KW | 27 KW | 36 KW | 54 KW | 72 KW | 90 KW | 108 KW |
Rated current | 15 A | 30 A | 45 A | 60 A | 91 A | 120 A | 152 A | 182 A |
Output power factor | 0.9 | |||||||
Rated input voltage | 380 Vac ± 20% | |||||||
Rated output voltage | 380 Vac ± 1% | |||||||
Battery voltage | 360 Vdc | |||||||
Number of battery | 12 Vdc * 30 pcs / 2 Vdc * 180 pcs | |||||||
Operating mode | AC and PV complementation | |||||||
PV INPUT | ||||||||
Max. voltage (Voc) | 750 Vdc | |||||||
Optimum operating voltage (Vmp) | 450 ~ 550 Vdc | |||||||
Max. conversion efficiency | ≥ 98% | |||||||
Floating charge voltage (25℃) | 414 Vdc ± 1% | |||||||
Equalizing charge voltage (25℃) | 428 Vdc ± 1% | |||||||
MPPT Max. current | 60 A | 120 A | 180 A | 240 A | 300 A | 360 A | ||
Max. PV power | 25 KW | 2 * 25 KW | 3 * 25 KW | 4 * 25 KW | 5 * 25 KW | 6 * 25 KW | ||
Number of PV input | 1 | 2 + 1 (reserve) | 3 + 1 (reserve) | 4 + 2 (reserve) | 5 + 3 (reserve) | 6 + 2 (reserve) | ||
MPPT modules | 1 | 2 + 1 (reserve) | 3 + 1 (reserve) | 4 + 2 (reserve) | 5 + 3 (reserve) | 6 + 2 (reserve) | ||
AC RECTIFIER | ||||||||
Input voltage range | 380 V ± 20% three-phase | |||||||
Rated frequency | 50 Hz / 60 Hz ± 5 Hz (settable) | |||||||
Power factor | 0.8 | |||||||
Floating charge voltage (25℃) | 410 V ± 1% | |||||||
Equalizing charge voltage (25℃) | 415 V ± 1% | |||||||
Max. charging current | 12 A | 25 A | 38 A | 50 A | 75 A | 167 A | 208 A | 250 A |
INVERTER | ||||||||
Inverter voltage | 380 Vac three-phase + N+PE | |||||||
Phase voltage | 220 / 230 / 240 Vac (settable) | |||||||
Output voltage precision | ± 1% | |||||||
Transient voltage range | ± 5% | |||||||
Transient recovery time | 20 ms | |||||||
Rated frequency | 50 Hz / 60 Hz ± 1 Hz (settable) | |||||||
Frequency tracking range | 50 Hz / 60 Hz ± 3 Hz | |||||||
Peak factor | 3 : 1 | |||||||
Waveform | Sinusoidal | |||||||
Waveform distortion | ≤ 3% (linear load) | |||||||
Voltage unbalance | ± 3% (100% unbalanced load) | |||||||
Overload | ≥ 105% ~ 110% for 1 h; ≥ 110% ~ 125% for 10 mins; ≥ 125% ~ 150% for 1 min; ≥ 150% shut down in 10 s; ≥ 200% shut down immediately; | |||||||
Short circuit | Current-limiting, shut down immediately until the user start up | |||||||
Max. efficiency | ≥ 90% | ≥ 91% | ≥ 92% | ≥ 93% | ||||
BYPASS | ||||||||
Rated voltage | 380 Vac three-phase + N+PE | |||||||
Voltage range | ± 20% | |||||||
Rated frequency | 50 Hz / 60 Hz ± 5 Hz | |||||||
Max. current | 19 A | 38 A | 57 A | 76 A | 114 A | 152 A | 190 A | 228 A |
BATTERIES MANAGEMENT | ||||||||
EOD voltage settings | 1.58 Vdc ~ 1.83 Vdc (settable), 1.75 Vdc (default) | |||||||
Staggering DOD (Depth of Discharge) settings | 1.85 Vdc ~ 2.1 Vdc (settable), 1.89 Vdc (default) | |||||||
Charging current settings | Factory default 0.15 C10; 0.07 ~ 0.3 C10 (settable) | |||||||
Battery management | Auto-transfer between equalizing charge and floating charge; Auto- temperature compensation of batteries | |||||||
TRANSFER TIME | ||||||||
Inverter – Bypass | 0 ms | |||||||
Bypass – Inverter | 0 ms | |||||||
COMMUNICATIONS | ||||||||
Remote control | Inverter startup, shutdown, abnormal clearance, EPO, battery self-test | |||||||
Communication interface | RS232, RS485, SNMP (optional) | |||||||
Dry contacts output | Bypass input abnormal, rectifier input abnormal, system fault, system alarm, low battery, output overload, fan fault, generator ON / OFF | |||||||
OTHERS | ||||||||
Operating temperature | 0℃ ~ 40℃ | |||||||
Max. relative humidity | 90% (non-condensing) | |||||||
Max. altitude | 1000 m at rated power (derating 1% for each additional 100 m); Max. 4000 m | |||||||
Noise level at 1 m | ≤ 65 dB (varies with loads and temperature) | |||||||
IP rating | IP20 | |||||||
Dimensions (W × D × H) (mm) | 450 × 840 × 1100 | 600 × 700 × 1750 | 960 × 800 × 1700 | |||||
Packaged dimensions (W × D × H) (mm) | 530 × 920 × 1140 | 690 × 790 × 1850 | 1040 × 890 × 1750 | |||||
Weight (kg) | 230 | 245 | 380 | 430 | 515 | 760 | 800 | 860 |